Abstract
The desiccant-based air-conditioning system consists of many heat and mass transfer components operating together with air fans. The performance test using the multiple tracer gas dilution method is important for knowing the internal and external flow rates, including the air leakages. The results of the test show the actual internal air flow rates and the sources of air leakage, and also show the interaction of air in the air-conditioned lecture room and in the mechanical room. The performance test using the multiple tracer gas dilution method in air flow and air leakages is important for a detailed evaluation of any air-conditioning system such as this desiccant-based one.
Original language | English |
---|---|
Article number | 1550027 |
Journal | International Journal of Air-Conditioning and Refrigeration |
Volume | 23 |
Issue number | 4 |
DOIs | |
Publication status | Published - 2015 Dec 1 |
Keywords
- HVAC system
- Tracer gas
- air flow diagnostics
- desiccant materials
- evaporation