Comfort near cold perimeter walls through radiant ceiling panel and other compensation methods

Larry G. Berglund, Hiroshi Yoshino, Satoru Kuno

Research output: Contribution to journalConference article

Abstract

Thermal discomfort can occur near a glass curtain wall in winter because of increased radiant heat loss from the occupant to the cold wall. The discomfort from the decrease in mean radiant temperature caused by the cold surface can be compensated for by raising the local air, ceiling, or floor temperature. In a field test, all of the compensation methods worked, with the subjects preferring the radiant ceiling panel system. For radiant compensation, the location, size, and panel surface temperature are designed and adjusted to raise the local mean radiant and, thereby, the operative temperature of the occupied area to comfort levels. Such panels are best controlled by systems that sense both radiant and air temperature as used in the determination of operative temperature.

Original languageEnglish
Pages (from-to)209-216
Number of pages8
JournalIAQ Conference
Publication statusPublished - 1997 Dec 1
EventConference on Design, Construction, and Operation of Healthy Buildings: Solutions to Global and Regional Concerns, IAQ 1997 - Washington, DC, United States
Duration: 2007 Sep 12007 Sep 1

ASJC Scopus subject areas

  • Building and Construction
  • Environmental Engineering
  • Public Health, Environmental and Occupational Health

Fingerprint Dive into the research topics of 'Comfort near cold perimeter walls through radiant ceiling panel and other compensation methods'. Together they form a unique fingerprint.